Inline duct fans [Fans, Pumps, Compressors] |
Selection
In almost all cases, the capacity of the inverter is the same as the motor capacity.
However if you have a fixed acceleration/deceleration time, the inverter capacity should be larger than the motor capacity.
|
Please confirm your motor's rated current.
[Motor's rated current] x 1.05 < [Inverter's rated current]
When you connect several motors to one inverter, please confirm the following:
[Total motor's rated current] x 1.1 < [Inverter's rated current]
In this case, the electric thermal function in the inverter can't protect all motors.
Please install an external thermal relay for each motor.
|
|