Mixers usually use the following operating methods:
- RUN and STOP operations by remote control
- Frequency setting by external analog input
- Vector control without sensor
- Emergency stop signal input
- Analog output for frequency meter
Connection diagram of inverters (VF-S15) Setting table for inverters (VF-S15)
Title
Function
Setting range
Recommended setting
Automatic torque boost
0 to 3
2
Command mode selection
0 to 4
0
Frequency setting mode selection 1
0 to 6
1 (VIA)
Meter adjustment
-
-
Base frequency 1
25 to 500Hz
Depends on the motor
Base frequency voltage 1
50-330 (240V class) 50-660 (500/600V class)
Depends on the motor
Input terminal selection 6 (S3)
0 to 203
20
Motor rated capacity
0.01 to 22kW
Depends on the motor
Motor rated current
0.1 to 100A
Depends on the motor
Motor rated speed
100 to 64000-1
Depends on the motor
Note
After setting these parameters, please perform the following steps:
(1) Connect the motor wiring.
(2) Turn on the start signal.