Winders [Textile machines]
|
Application samples
Winders usually use the following operating methods:
- Frequency setting through RS485 communication (Inter-drive communication)
Master drive: Input RUN/STOP operation and frequency setting.
Slave drives: Receive frequency reference from a master drive.
- Emergency stop signal input
- Regenerative power ridethrough control (deceleration stop)
Notice: When using VFS11 with RS485 communication, it is necessary to install an RS485 communication board (RS4003Z: Optional devices).
What is RS4003Z for VFS11?
RS4003Z for VFS11 can support the RS485 communication protocol with PLCs and computers.
On RS485 networks, RS4003Z allows for a maximum of 32 connections.

Connection diagram of inverters (VFS11: Master drive)
Frequency settings for each inverter use the following methods:
Master drive: External potentiometer
Slave drives: Inter-drive communication
Notice:
The RS4003Z is a built-in terminal board that is used in place of a standard terminal board.
When you use RS485 communication, please make sure to connect the RS485 wiring to the correct terminal block.

Setting table for inverters (VFS11)
- Master drive
The master drive sends frequency reference to slave drives.
| Title |
Function |
Setting range |
Recommended setting |
    |
Command mode selection |
0 to 1 |
0 |
    |
Frequency setting mode selection 1 |
0 to 6 |
2 |
    |
Input terminal selection 6 (S3) |
0 to 65 |
11 |
    |
Regenerative power ridethrough control (Deceleration stop) |
0 to 2 |
2 |
    |
Setting of master and slaves for communication between inverters |
0 to 4 |
3 |
- Slave drives
Slave drives receive frequency reference from the master drive.
The communication error trip time is useful in case a communication cable becomes disconnected or is accidentaly cut.
When the master drive trips occur, you can stop all slave drives using the F806 function.
| Title |
Function |
Setting range |
Recommended setting |
    |
Command mode selection |
0 to 1 |
0 |
    |
Frequency setting mode selection 1 |
0 to 6 |
4 |
    |
Input terminal selection 6 (S3) |
0 to 65 |
11 |
    |
Regenerative power ridethrough control (Deceleration stop) |
0 to 2 |
2 |
    |
Communication error trip time |
0: Disabled, 1 to 100 sec |
1 |
    |
Setting of master and slave for communication between inverters |
0 to 4 |
2 |
Special functions of VFAS1 for textile machines
The VFAS1 series has special functions for textile machines.
1. Synchronized deceleration time
(time elapsed between start of deceleration to stop)
2. Traverse function
|
|
|