Toshiba Toshiba Schneider Inverter Corporation

Compact TOSVERT VF-S15

Input voltage/Capacity range
1 phase 240V-0.2~2.2kW
3 phase 240V-0.4~15kW
3 phase 500V-0.4~15kW
多機能・小型 TOSVERT VF-S15

Common specificaitons

Item Specification
Principal
control
functions
Control system Sinusoidal PWM control
Output voltage range Note1) Adjustable within the range of 50 to 330V (240V class) and 50 to 660V (500V class) by correcting the supply voltage
Output frequency range 0.1 to 500.0Hz, default setting: 0.5 to 80Hz, maximum frequency: 30 to 500Hz
Minimum setting steps of frequency 0.1Hz: analog input (when the max. frequency is 100Hz), 0.01Hz: Operation panel setting and communication setting.
Frequency accuracy Digital setting: within +/-0.01% of the max. frequency (-10 to +/-60 degree C)
Analog setting: within +/-0.5% of the max. frequency (25 degreeC +/-10 degree C) Note 2)
Voltage/frequency characteristics V/f constant, variable torque, automatic torque boost, vector control, automatic energy-saving. dynamic automatic energy-saving control (for fan and pump), PM motor control, V/F 5-point setting, Auto-tuning. Base frequency (20- 500Hz) adjusting to 1 & 2, torque boost (0-30%) adjusting to 1 & 2, adjusting frequency at start (0.1-10Hz)
Frequency setting signal Setting dial on the front panel, external frequency potentiometer (connectable to a potentiometer with a rated impedance of 1k-10k ohm), 0-10Vdc / -10-+10Vdc (input impedance: 30k ohm), 4-20mAdc (Input impedance: 250 ohm).
Terminal block base frequency The characteristic can be set arbitrarily by two-point setting. Possible to set: analog input (VIA, VIB, VIC).
Frequency jump Three frequencies can be set. Setting of the jump frequency and the range.
Upper- and lower-limit frequencies Upper-limit frequency: 0.5 to max. frequency, lower-limit frequency: 0 to upper-limit frequency
PWM carrier frequency Adjustable range of 2.0k to 16.0kHz (default: 12.0kHz).
PID control Setting of proportional gain, integral gain, differential gain and control waiting time. Checking whether the amount of processing amount and the amount of feedback agree.
Operation
specifications
Acceleration/deceleration time Selectable from among acceleration/deceleration times 1 & 2 & 3 (0.0 to 3600 sec.). Automatic acceleration/deceleration function. S-pattern acceleration/deceleration 1 & 2 and S-pattern adjustable. Control of forced rapid deceleration and dynamic rapid deceleration.
DC braking Braking start-up frequency: 0 to maximum frequency, braking rate: 0 to 100%, braking time: 0 to 25.5 seconds, emergency DC braking, motor shaft fixing control.
Dynamic Braking Drive Circuit Control and drive circuit is built in the inverter with the braking resistor outside (optional).
Input terminal function
(programmable)
Possible to select from among about 110 functions, such as forward/reverse run signal input, jog run signal input, operation base signal input and reset signal input, to assign to 8 input terminals. Logic selectable between sink and source.
Output terminal functions
(programmable)
Possible to select from among about 150 functions, such as upper/lower limit frequency signal output, low speed detection signal output, specified speed reach signal output and failure signal output, to assign to FL relay output, open collector output terminal, and RY output terminals.
Forward/reverse run The RUN and STOP keys on the operation panel are used to start and stop operation, respectively. Forward/reverse run possible through communication and logic inputs from the terminal block.
Jog run Jog mode, if selected, allows jog operation from the terminal block and also from remote keypad.
Preset speed operation Frequency references + 15-speed operation possible by changing the combination of 4 contacts on the terminal block.
Retry operation Capable of restarting automatically after a check of the main circuit elements in case the protective function is activated. 10 times (Max.) (selectable with a parameter)
Various prohibition settings/
Password setting
Possible to write-protect parameters and to prohibit the change of panel frequency settings and the use of operation panel for operation, emergency stop or resetting. Possible to write-protect parameters by setting 4 digits password and terminal input.
Regenerative power
ride-through control
Possible to keep the motor running using its regenerative energy in case of a momentary power failure (default: OFF).
Auto-restart operation In the event of a momentary power failure, the inverter reads the rotational speed of the coasting motor and outputs a frequency appropriate to the rotational speed in order to restart the motor smoothly. This function can also be used when switching to commercial power.
Light-load high-speed operation Increases the operating efficiency of the machine by increasing the rotational speed of the motor when it is operated under light load.
Drooping function When two or more inverters are used to operate a single load, this function prevents load from concentrating on one inverter due to unbalance.
Override function External input signal adjustment is possible to the operation frequency command value.
Relay output signal 1c- contact output and 1a- contact output Note 3)
Maximum switching capacity : 250Vac-2A , 30Vdc-2A (At resistive load cos=1),
250Vac-1A (cos=0.4) , 30Vdc-1A (L/R=7ms)
Minimum permissible load : 5Vdc-100mA, 24Vdc-5mA
Protective
function
Protective function Stall prevention, current limitation, over-current, output short circuit, over-voltage, over-voltage limitation, undervoltage, ground fault detection, input phase failure, output phase failure, overload protection by electronic thermal function, armature over-current at start-up, load side over-current at start-up, over-torque, undercurrent, overheating, cumulative operation time, life alarm, emergency stop, braking resistor over-current/ overload, various pre-alarms
Electronic thermal characteristic Switching between standard motor and constant-torque VF motor, switching between motors 1 & 2, setting of overload trip time, adjustment of stall prevention levels 1 & 2, selection of overload stall
Reset function Panel reset / External signal reset / Power supply reset. This function is also used to save and clear trip records.
Display
function
Alarms Overcurrent, overvoltage, overload, overheat, communication error, under-voltage, setting error, retry in process, upper/lower limits
Causes of failures Overcurrent, overvoltage, overheat, output short-circuit, ground fault, overload on inverter, arm overcurrent at startup, overcurrent on the load side at start-up, CPU fault, EEPROM fault, RAM fault, ROM fault, communication error. (Selectable: dynamic braking resistor overload, emergency stop, under-voltage, small current, over-torque, lowtorque, motor overload, input phase failure, output phase failure)
Monitoring function Output frequency, frequency command value, operation frequency command, forward/reverse run, output current, input voltage (DC detection), output voltage, torque, inverter load factor, motor load factor, braking resistor load factor, input power, output power, information on input terminals, information on output terminals, overload and region setting, version of CPU1, version of CPU2, PID feedback value, stator frequency, causes of past trips 1to 8, parts replacement alarm, cumulative operation time, number of starting
Past trip monitoring function Stores data on the past eight trips: number of trips that occurred in succession, output frequency, frequency command value, forward/reverse run, output current, input voltage (DC detection), output voltage, information on input terminals, information on output terminals, and cumulative operation time when each trip occurred.
Output for frequency meter Analog output for meter: 1mA dc full-scale dc ammeter
0 - 20mA (4 to 20mA) output: DC ammeter (allowable load resistance: Less than 600 ohm)
0 - 10V output: DC voltmeter (allowable load resistance: Over 1k ohm)
Maximum resolution: 1/1000
4-digit 7-segments LED Frequency: inverter output frequency.
Alarm: stall alarm "C", overvoltage alarm "P", overload alarm "L", overheat alarm "H", communication alarm "t".
Status: inverter status (frequency, cause of activation of protective function, input/output voltage, output current, etc.) and parameter settings.
Free-unit display: arbitrary unit (e.g. rotating speed) corresponding to output frequency.
Indicator Lamps indicating the inverter status by lighting, such as RUN lamp, MON lamp, PRG lamp, % lamp, Hz lamp. The charge lamp indicates that the main circuit capacitors are electrically charged.
Safety function Safe Torque Off(STO) function according to EN/IEC 61508 SIL2 and ISO 13849-1 category 3 PL "d".
Environments Location of use Indoors; not exposed to direct sunlight, corrosive gas, explosive gas, flammable gas, oil mist, or dust; and vibration of less than 5.9m/s2 (10 to 55Hz).
Elevation 3000 m or less (current reduction required over 1000 m) Note 4)
Ambient temperature -10 to +60 degree C Note 5)
Storage temperature -25 to +70 degree C
Relative humidity 5 to 95% (free from condensation and vapor).

Note 1. Maximum output voltage is the same as the input voltage.
Note 2. It is necessary to finely adjust Bias and Gain parameters of each analog input.
Note 3. A chattering (momentary ON/OFF of contact) is generated by external factors of the vibration and the impact, etc. In particular, please set the filter of 10ms or more, or timer for measures when connecting it directly with input unit terminal of programmable controller. Please use the OUT terminal as much as possible when the programmable controller is connected.
Note 4. Current must be reduced by 1% for each 100 m over 1000 m. For example, 90% at 2000m and 80% at 3000m.
Note 5. When using the inverter in locations with temperatures above 40°C, remove the protective label on the top of the inverter and use the inverter with the output current reduced according to section 6.18 in user manual. To align the inverters side-by-side horizontally, remove the protective label on the top of the inverter before use. When using the inverter in locations with temperatures above 40°C, use the inverter with the output current reduced.