EMI filter (EMC Directive compliant noise reduction filter)
Most of all Toshiba inverters has a built-in EMC noise filter.
When you need to comply with a higher standard or to use longer motor cable, please use an external EMI filter.
TOSVERT VF-AS1
For 200V class 0.4 to 7.5kW and 400V class 0.75 to 500kW, EMC noise filter is built-in standard.
Please use external options depended on the length of the cable between inverter and motor.
Regarding type-form, dimensions and connection diagram, please refer catalogue pages. [VF-AS1 catalogue]
| Inverter type |
Requirements |
Conducted noise
IEC61800-3 category C2
(EN55011 classA Group1)
|
Conducted noise
IEC61800-3 category C3
(EN55011 classA Group2)
|
PWM carrier
frequency
(kHz)
|
Length of motor
connecting
cable(m)
|
| VFAS1-2004PL-2022PL | 4 | 10 | Built-in filter | - |
| VFAS1-4007PL-4037PL | 16 | 5 |
| VFAS1-2037PL-2075PL | 4 | 10 | - | Built-in filter |
| VFAS1-4055PL-4150PL | 16 | 5 |
| VFAS1-4185PL-4750PL | 2.5 | 25 |
| 16 | 25 |
| VFAS1-4900PC-4500KPC | 2.5 | 50 |
TOSVERT VF-PS1
For 200V class 0.4 to 7.5kW and 400V class 0.75 to 630kW, EMC noise filter is built-in standard.
Please use external options depended on the length of the cable between inverter and motor.
Regarding type-form, dimensions and connection diagram, please refer catalogue pages. [VF-PS1 catalogue]
| Inverter type |
Requirements |
Conducted noise
IEC61800-3 category C2
(EN55011 classA Group1)
|
Conducted noise
IEC61800-3 category C3
(EN55011 classA Group2)
|
PWM carrier
frequency
(kHz)
|
Length of motor
connecting
cable(m)
|
| VFPS1-2004PL-2022PL | 4 | 10 | Built-in filter | - |
| VFPS1-4007PL-4037PL | 16 | 5 |
| VFPS1-2037PL-2075PL | 4 | 10 | - | Built-in filter |
| VFPS1-4055PL-4150PL | 16 | 5 |
| VFPS1-4185PL-4750PL | 2.5 | 25 |
| VFPS1-4185PL-4750PL | 16 | 25 |
| VFPS1-4900PC-4630KPC | 2.5 | 50 |
TOSVERT VF-FS1, VF-S11
A high-attenuation compact EMI noise filter that can be
Foot-mounted and Side-mounted. With this filter on,
the inverter complies with the higher standards.
|
|
TOSVERT VF-S11 IP20 model
Single-phase 200V, three-phase 400V model:
EN55011 Class A Group 1(Motor connecting cable length: 5 m or less)
TOSVERT VF-FS1 IP20 model (up to 5.5kW)
EN61800-3, 1st Environment, C2(Motor connecting cable length: 5 m or less): up to 5.5kW
EN61800-3, 1st Environment, C3(Motor connecting cable length: 5 m or less): over 7.5kW
Regarding type-form, dimensions and connection diagram, please refer catalogue pages.
[VF-FS1 catalogue],
[VF-S11 catalogue]
|
TOSVERT VF-PS1, VF-FS1 IP54 model
The IP54 model of TOSVERT VF-PS1, VF-FS1 comply with IEC61800-3 by a built-in EMC filter.
PLE model: Complied with EN55011 class A
PDE model: Complied with EN55011 class B
|