- Standard specificaitons -
Three-phase 200V
|
Item
|
Specification
|
|
Input voltage
|
3-phase 200V
|
|
Applicable motor (kW)
|
0.1
|
0.2
|
0.4
|
0.75
|
1.5
|
2.2
|
|
Rating
|
Type
|
VFNC1-
|
|
Form
|
2001P
|
2002P
|
2004P
|
2007P
|
2015P
|
2022P
|
|
Capacity (kVA) Note 1)
|
0.3
|
0.6
|
1.0
|
1.6
|
2.9
|
3.9
|
|
Rated output current (A) Note 2)
|
0.7
|
1.4
|
2.4
|
4
|
7.5
|
10.0
|
|
Rated output voltage Note 3)
|
3-phase 200V to 240V
|
|
Overload current rating
|
60 seconds at 150%
|
|
Power supply
|
Voltage-frequency
|
3-phase 200V to 240V - 50/60Hz
|
|
Allowable fluctuation
|
Voltage +10%, -15% Note 4), frequency+/-5%
|
|
Protective method
|
IP20 Enclosed type (JEM 1030)
|
|
Cooling method
|
Self-cooling
|
Forced air-cooled
|
|
Color
|
Munsel 5Y8/0.5
|
|
Charge lamp
|
LED indicating the charge status of the capacitor in the main circuit
|
1-phase 200V
|
Item
|
Specification
|
|
Input voltage
|
1-phase 200V
|
|
Applicable motor (kW)
|
0.1
|
0.2
|
0.4
|
0.75
|
1.5
|
2.2
|
|
Rating
|
Type
|
VFNC1S-
|
|
Form
|
-
|
2002P
|
2004P
|
2007P
|
2015P
|
2022P
|
|
Capacity (kVA) Note 1)
|
-
|
0.6
|
1.0
|
1.6
|
2.9
|
3.9
|
|
Rated output current (A) Note 2)
|
-
|
1.4
|
2.4
|
4
|
7.5
|
10.0
|
|
Rated output voltage Note 3)
|
3-phase 200V to 240V
|
|
Overload current rating
|
60 seconds at 150%
|
|
Power supply
|
Voltage-frequency
|
1-phase 200V to 240V - 50/60Hz
|
|
Allowable fluctuation
|
Voltage +10%, -15% Note 4), frequency +/-5%
|
|
Protective method
|
IP20 Enclosed type (JEM 1030)
|
|
Cooling method
|
-
|
Self-cooling
|
Forced air-cooled
|
|
Color
|
Munsel 5Y8/0.5
|
|
Charge lamp
|
LED indicating the charge status of the capacitor in the main circuit
|
1-phase 100V
|
Item
|
Specification
|
|
Input voltage
|
1-phase 100V
|
|
Applicable motor (kW)
|
0.1
|
0.2
|
0.4
|
0.75
|
1.5
|
2.2
|
|
Rating
|
Type
|
VFNC1S-
|
|
Form
|
1001P
|
1002P
|
1004P
|
1007P
|
-
|
-
|
|
Capacity (kVA) Note 1)
|
0.3
|
0.6
|
1.0
|
1.6
|
-
|
-
|
|
Rated output current (A) Note 2)
|
0.7
|
1.4
|
2.4
|
4
|
-
|
-
|
|
Rated output voltage Note 3)
|
3-phase 200V to 230V
|
|
Overload current rating
|
60 seconds at 150%
|
|
Power supply
|
Voltage-frequency
|
1-phase 100V to 115V - 50/60Hz
|
|
Allowable fluctuation
|
Voltage +10%, -15% Note 4), frequency +/-5%
|
|
Protective method
|
IP20 Enclosed type (JEM 1030)
|
|
Cooling method
|
Self-cooling
|
Forced air-cooled
|
-
|
-
|
|
Color
|
Munsel 5Y8/0.5
|
|
Charge lamp
|
LED indicating the charge status of the capacitor in the main circuit
|
1-phase 200V (built-in EMI noise filter)
|
Item
|
Specification
|
|
Input voltage
|
1-phase 200V (built-in EMI noise filter)
|
|
Applicable motor (kW)
|
0.1
|
0.2
|
0.4
|
0.75
|
1.5
|
2.2
|
|
Rating
|
Type
|
VFNC1S-
|
|
Form
|
-
|
2002PL
|
2004PL
|
2007PL
|
2015PL
|
2022PL
|
|
Capacity (kVA) Note 1)
|
-
|
0.5
|
0.9
|
1.6
|
2.9
|
4.1
|
|
Rated output current (A) Note 2)
|
-
|
1.2
|
2.3
|
4
|
7.5
|
10.7
|
|
Rated output voltage Note 3)
|
3-phase 200V to 240V
|
|
Overload current rating
|
60 seconds at 150%
|
|
Power supply
|
Voltage-frequency
|
1-phase 200V to 240V - 50/60Hz
|
|
Allowable fluctuation
|
Voltage +10%, -15% Note 4), frequency +/-5%
|
|
Protective method
|
IP20 Enclosed type (JEM 1030)
|
|
Cooling method
|
-
|
Self-cooling
|
Forced air-cooled
|
|
Color
|
Munsel 5Y8/0.5
|
|
Charge lamp
|
None
|
|
Built-in filter
|
EMI noise filter (EN55011 Group1 ClassB)
|
Note) 1. Capacity is calculated at 220V for the 200V models.
Note) 2. Indicates rated output current setting when the PWM carrier frequency (parameter F300) is 4kHz or less.
If the PWM carrier frequency setting is fixed above 4kHz, the rated current needs to be reduced. If the PWM carrier frequency is set above 4kHz, it could fall automatically if an over-current flaws
during acceleration or for any other reason, depending on the amount of current that flows.
The default setting of the PWN carrier frequency is 12kHz.
Note) 3. Maximum output voltage is the same as the input voltage. The maximum output voltage of a single-phase 100V model is proportional to the supply voltage.
With regard to 100V models, the output voltage may decrease about 10 to 20% if motor load is applied.
When operating VF-nC1 in conjunction with general purpose motor (200V), it is necessary to reduce the motor load.
Note) 4. +/-10% when the inverter is used continuously (load of 100%).