Standard specificaitons
3-phase 240V
Item |
Specification |
Input voltage class |
3-phase 240V |
Applicable motor (kW) |
0.4 |
0.55 |
0.75 |
1.5 |
2.2 |
4.0 |
5.5 |
7.5 |
11 |
15 |
Rating |
Type |
VFS11- |
Form |
2004PM |
2005PM |
2007PM |
2015PM |
2022PM |
2037PM |
2055PM |
2075PM |
2110PM |
2150PM |
Capacity (kVA) Note 1) |
1.3 |
1.4 |
1.8 |
3.0 |
4.2 |
6.7 |
10 |
13 |
21 |
25 |
Rated output current
(A) Note 2) |
3.3
(3.3) |
3.7
(3.3) |
4.8
(4.4) |
8.0
(7.9) |
11.0
(10.0) |
17.5
(16.4) |
27.5
(25.0) |
33
(33) |
54
(49) |
66
(60) |
Output voltage Note 3) |
3-phase 200V to 240V |
Overload current rating |
150%-60 seconds, 200%-0.5 second Note 4) |
Power supply |
Voltage-frequency |
3-phase 200V to 240V - 50/60Hz |
Allowable fluctuation |
Voltage + 10%, -15% Note 5), frequency +/-5% |
Protective method |
IP20 Enclosed type (JEM1030) |
Cooling method |
Self-cooling |
Forced air-cooled |
Color |
Munsel 5Y-8/0.5 |
Built-in filter |
Basic filter Note 7) |
3-phase 500V
Item |
Specification |
Input voltage class |
3-phase 500V |
Applicable motor (kW) |
0.4 |
0.75 |
1.5 |
2.2 |
4.0 |
5.5 |
7.5 |
11 |
15 |
Rating |
Type |
VFS11- |
Form |
4004PL |
4007PL |
4015PL |
4022PL |
4037PL |
4055PL |
4075PL |
4110PL |
4150PL |
Capacity (kVA) Note 1) |
1.1 |
1.8 |
3.1 |
4.2 |
7.2 |
11 |
13 |
21 |
25 |
Rated output current (A) Note 2) |
1.5
(1.5) |
2.3
(2.1) |
4.1
(3.7) |
5.5
(5.0) |
9.5
(8.6) |
14.3
(13.0) |
17.0
(17.0) |
27.7
(25.0) |
33
(30) |
Output voltage Note 3) |
3-phase 380V to 500V |
Overload current rating |
150%-60 seconds, 200% -0.5 second Note 4) |
Power supply |
Voltage-frequency |
3-phase 380V to 500V - 50/60Hz |
Allowable fluctuation |
Voltage + 10%, -15% Note 5), frequency +/-5% |
Protective method |
IP20 Enclosed type (JEM1030) |
Cooling method |
Forced air-cooled |
Color |
Munsel 5Y-8/0.5 |
Built-in filter |
High-attenuation EMI filter Note 8) |
1-phase 240V, 3-phase 600V
Item |
Specification |
Input voltage class |
1-phase 240V |
3-phase 600V Note 6) |
Applicable motor (kW) |
0.2 |
0.4 |
0.75 |
1.5 |
2.2 |
0.75 |
1.5 |
2.2 |
4.0 |
5.5 |
7.5 |
11 |
15 |
Rating |
Type |
VFS11S- |
VFS11 |
Form |
2002PL |
2004PL |
2007PL |
2015PL |
2022PL |
6007P |
6015P |
6022P |
6037P |
6055P |
6075P |
6110P |
6150P |
Capacity (kVA) Note 1) |
0.6 |
1.3 |
1.8 |
3.0 |
4.2 |
1.7 |
2.7 |
3.9 |
6.1 |
9.0 |
11 |
17 |
22 |
Rated output current
(A) Note 2) |
1.5 (1.5) |
3.3 (3.3) |
4.8 (4.4) |
8.0 (7.9) |
11.0 (10.0) |
1.7 (1.5) |
2.7 (2.4) |
3.9 (3.5) |
6.1 (5.5) |
9.0 (8.1) |
11.0 (9.9) |
17.0 (15.3) |
22.0 (19.8) |
Output voltage Note 3) |
3-phase 200V to 240V |
3-phase 525V to 600V |
Overload current rating |
150%-60 seconds, 200%-0.5 second Note 4) |
150%-60 seconds, 200%-0.5 second Note 4) |
Power supply |
Voltage-frequency |
1-phase 200V to 240V . 50/60Hz |
3-phase 525V to 600V . 50/60Hz |
Allowable fluctuation |
Voltage + 10%, -15% Note 5), frequency+/-5% |
Voltage + 10%, -15% Note 5), frequency+/-5% |
Protective method |
IP20 Enclosed type (JEM1030) |
IP20 Enclosed type (JEM1030) |
Cooling method |
Self-cooling |
Forced air-cooled |
Forced air-cooled |
Color |
Munsel 5Y-8/0.5 |
Munsel 5Y-8/0.5 |
Built-in filter |
High-attenuation EMI filter Note 8) |
No filter |
Note 1. Capacity is calculated at 220V for the 240V class, at 440V for the 500V class and at 575V for the 600V models.
Note 2. Indicates rated output current setting when the PWM carrier frequency (parameter F300) is 4kHz or less.
When exceeding 4kHz, the rated output current setting is indicated in the parenthesis. When the input power voltage of the 500V class model exceeds 480V, it is necessary to further reduce the setting. The default
setting of the PWM carrier Frequency is 12kHz.
Note 3. Maximum output voltage is the same as the input voltage.
Note 4. May differ according to voltage and model.
Note 5. +/-10% when the inverter is used continuously (load of 100%).
Note 6. If you are using 600V model, be sure to connect an input reactor (ACL).
Note 7. Built-in standard filter: Core and capacitors, with RFI noise filter option: Complies IEC61800-3 categoly C2 (Max.5m*) and IEC61800-3 categoly C1 (Max.1m*)
* Length of motor connecting cable.
Note 8. Built-in high-attenuation EMI filter: Complies IEC61800-3 categoly C2 for 240V class 0.2-1.5kW and 500V class 0.4-4.0kW, IEC61800-3 categoly C3 for 240V class 2.2kW and 500V class 5.5-15kW
(Max.5m*)
With RFI noise filter option : Complies IEC61800-3 categoly CI (Max.20m*) and IEC61800-3 categoly C2 (Max.50m*)* Length of motor connecting cable.
Note 9. Above 40 degreeC : Remove the protective seal from the top of the inverter. Above 50 degreeC: Remove the seal from the top of the inverter and use the inverter with the rated output current reduced.
Note 10. If inverters are installed side by side (with no sufficient space left between them) installation: Remove the seal from the top of each inverter.
When installing the inverter where the ambient temperature will rise above 40 degreeC, remove the seal from the top of the inverter and use the inverter with the rated output current reduced.
Totally-Enclosed Box Type Inverter: IP54
Item |
Specification |
Input voltage class |
1-phase 240V class/3-phase 240V class/3-phase 500V class |
Applicable motor (kW) |
0.2 |
0.4 |
0.75 |
1.5 |
2.2 |
4.0 |
Model |
Voltage class |
Model number |
VFS11S/VFS11 |
1-phase 240V class |
VFS11S- |
2002PLE |
2004PLE |
2007PLE |
2015PLE |
2022PLE |
- |
3-phase 240V class |
VFS11- |
- |
2004PME |
2007PME |
2015PME |
2022PME |
2037PME |
3-phase 500V class |
VFS11- |
- |
- |
4007PLE |
4015PLE |
4022PLE |
4037PLE |
Rating |
Capacity (kVA) |
Note 1: |
0.6 |
1.3 |
1.8 |
3.0/3.0/3.1 |
4.2 |
6.7/7.2 |
Output current (A)
Note 2: |
1-phase 240V |
1.5 (1.5) |
3.3 (3.3) |
4.8 (4.4) |
8.0 (7.9) |
11.0 (10.0) |
- |
3-phase 240V |
- |
3.3 (3.3) |
4.8 (4.4) |
8.0 (7.9) |
11.0 (10.0) |
17.5 (16.4) |
3-phase 500V |
- |
- |
2.3 (2.1) |
4.1 (3.7) |
5.5 (5.0) |
9.5 (8.6) |
Output voltage
Note 3: |
240V class: 3-phase 200 to 240V, 500V class: 3-phase 380 to 500V |
Overload current rating |
150%-1min., 200%-0.5 sec. (50%-reduction value) |
Power supply |
Voltage-frequency |
240V class: 1-phase/3-phase 200 to 240V-50/60Hz,
500V class: 3-phase 380 to 500V-50/60Hz |
Allowable fluctuation |
Voltage+10%, -15% Note 4:, Frequency+/-5% |
Protective method |
Totally enclosed type (JEM1030) compliant with IP54/possible to bring into compliance
with IP55 Note 5: |
Cooling method |
Self-cooled (with a built-in cooling fan. 1-phase/3-phase 240V-0.75kW or smaller:
Cooling fan not provided) |
Color |
Munsel 5Y-8/0.5 |
Built-in filter |
1-phase & 500V class: High-attenuation EMI filter, 3-phase 240V class: Standard filter |
Environments |
Use environments |
Indoor type. Altitude: Not more than 1000m.
Place free from corrosive and explosive gases |
Ambient temperature |
-10 to +40 degree |
Storage temperature |
-25 to +70 degree |
Relative humidity |
20 to 93% |
Vibration |
5.9m/s2 or less (10 to 55Hz) |
Note 1: Capacity is calculated at 220V for the 240V models and at 440V for the 500V models.
Note 2: Indicates rated output current setting when the PWM carrier frequency (parameter F300) is 4kHz or less.
The values between parentheses refer to output currents at PWM carrier frequencies of over 4kHz. They
need to be reduced further at frequencies over 12kHz (If a motor cable over 30m in length is used, it is
necessary to reduce them more. This means that the lives of the internal components will be shortened).
When the input power voltage of the 500V class model exceeds 480V, it is necessary to further reduce
the setting. The default setting of the PWM carrier frequency is 12kHz.
Note 3: The maximum output voltage is equal to the input supply voltage.
Note 4: +/-10% when the inverter is operated continuously (under a load of 100%).
Note 5: IP54-compliant structures refer to structures that protect the contents from dust and harmful effects of
water that drops from every direction.
The inverter can be brought into compliance with IP55 specifications by making the wiring port watertight.
(IP55-compliant structures refer to structures that protect the contents from dust and harmful effects of
water that comes in a jet from every direction.)
To bring the inverter into compliance with IP-55, use PG screw type cable grounds. Among cable grounds
available are skin-top grounds manufactured by LAPP (Germany).
Note 6: For control specifications, parameters and functions, refer to the instruction manual.
Note 7: The factory default settings of parameters are different from those of the VFS-11 standard
type.
Note 8: The inverter has a built-in cooling fan. The cooling fan has a useful life of approximately 30,000 hours (2
to 3 years when operated continuously), so it needs to be replaced periodically.
(Single/three-phase 240V-0.75kW models and smaller are not equipped with cooling fans.)
If the cooling fan does not operate normally, the temperatures of the internal electrical components will
rise high, and as a result their lives will be shortened. So inspect it periodically.
Note 9: The manual power ON-OFF switch has a useful life of approximately 5 years (if operated 12 hours per
day at an average yearly ambient temperature of 30 degreeC), so it needs to be replaced periodically.