Dryers [Farm machines]



 Selection

In almost all cases, the capacity of the inverter is the same as the motor capacity.
However if you have a fixed acceleration/deceleration time, the inverter capacity should be larger than the motor capacity.

Please confirm your motor's rated current.
 [Motor's rated current] x 1.05 < [Inverter's rated current]

When you connect several motors to one inverter, please confirm the following:
 [Total motor's rated current] x 1.1 < [Inverter's rated current]

In this case, the electric thermal function in the inverter can't protect all motors. Please install an external thermal relay for each motor.