Toshiba Toshiba Schneider Inverter Corporation
Not be provided in the Japanese market.

Multi-function Book type TOSVERT VF-MB1

Capacity range
1 phase 240V-0.2~2.2kW
3 phase 500V-0.4~15kW
Multi-function Book type TOSVERT VF-MB1

Standard specificaitons

1-phase 240V

Item Specification
Input voltage class 1-phase 240V class
Applicable motor (kW) 0.2 0.4 0.75 1.5 2.2
Rating Type VFMB1S-
Form 2002PL 2004PL 2007PL 2015PL 2022PL
Capacity (kVA) Note 1) 0.6 1.3 1.8 3.0 4.2
Rated output current
(A) Note 2)
1.5 (1.5) 3.3 (3.3) 4.8 (4.8) 8.0 (8.0) 11.0 (11.0)
Output voltage Note 3) 3-phase 200V to 240V
Overload current rating Note 2) 150%-60 seconds, 200%-0.5 second (120%-60 seconds, 165%-0.5 second)
Power supply Voltage-frequency 1-phase 200V to 240V - 50/60Hz
Allowable fluctuation Voltage 170 to 264V Note 4), frequency ±5%
Required Power supply
capacity (kVA) Note 5)
0.8 1.4 2.3 4.0 5.4
Protective method (IEC60529) IP20
Cooling method Forced air-cooled
Color RAL7016
Built-in fi lter EMC filter

3-phase 500V

Item Specification
Input voltage class 3-phase 500V class
Applicable motor (kW) 0.4 0.75 1.5 2.2 4.0 5.5 7.5 11 15
Rating Type VFMB1-
Form 4004PL 4007PL 4015PL 4022PL 4037PL 4055PL 4075PL 4110PL 4150PL
Capacity (kVA) Note 1) 1.1 1.8 3.1 4.2 7.2 11 13 21 25
Rated output current (A) Note 2) 1.5
(1.5)
2.3
(2.3)
4.1
(4.1)
5.5
(5.5)
9.5
(9.5)
14.3
(17.0)
17.0
(23.0)
27.7
(33.0)
33.0
(40.0)
Output voltage Note 3) 3-phase 380V to 500V
Overload current rating Note 2) 150%-60 seconds, 200%-0.5 second (120%-60 seconds, 165%-0.5 second)
Power supply Voltage-frequency 3-phase 380V to 500V - 50/60Hz
Allowable fluctuation Voltage 323 to 550V Note 4), frequency ±5%
Required Power supply
capacity (kVA) Note 5)
1.6 2.6 4.7 6.3 10.1 15.2 19.6 26.9 34.9
Protective method (IEC60529) IP20
Cooling method Forced air-cooled
Color RAL7016
Built-in filter EMC fi lter

Note 1. Capacity is calculated at 220V for the 240V models, at 440V for the 500V models.
Note 2. It is a value when the inverter overload characteristic selection (parameter aul) is the constant torque characteristic.
Value in ( ) for the variable torque characteristic.
The output current must be reduced according to the PWM carrier frequency, ambient temperature and supply voltage.
Note 3. Maximum output voltage is the same as the input voltage.
Note 4. At 180V-264V for the 240V models, at 342V-550V for the 500V models when the inverter is used continuously (load of 100%).
Note 5. Required power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).