Toshiba Toshiba Schneider Inverter Corporation

Compact TOSVERT VF-S15

Input voltage/Capacity range
1 phase 240V-0.2~2.2kW
3 phase 240V-0.4~15kW
3 phase 500V-0.4~15kW
TOSVERT VF-S15

Standard specificaitons

3-phase 240V

Item Specification
Input voltage class 3-phase 240V
Applicable motor (kW) 0.4 0.75 1.5 2.2 4.0 5.5 7.5 11 15
Rating Type VFS15-
Form 2004PM-W1 2007PM-W1 2015PM-W1 2022PM-W1 2037PM-W1 2055PM-W1 2075PM-W1 2110PM-W1 2150PM-W1
Capacity (kVA) Note 1) 1.3 1.8 3.0 4.2 6.7 10.5 12.6 20.6 25.1
Rated output current
(A) Note 2)
3.3
(3.3)
4.8
(4.4)
8.0
(7.9)
11.0
(10.0)
17.5
(16.4)
27.5
(25.0)
33
(33)
54
(49)
66
(60)
Rated Output voltage
Note 3)
3-phase 200V to 240V
Overload current rating 150%-60 seconds, 200%-0.5 second
Power
supply
Voltage-frequency 3-phase 200V to 240V - 50/60Hz
Allowable fluctuation Voltage 170V to 264V Note 4), frequency +/-5%
Required Power
supply
capacity (kVA) Note 5)
1.4 2.5 4.3 5.7 9.2 13.8 17.8 24.3 31.6
Protection degree (IEC60529) IP20
Cooling method Self-cooling Forced air-cooled
Color RAL7016
Built-in filter Basic filter

3-phase 500V

Item Specification
Input voltage class 3-phase 500V
Applicable motor (kW) 0.4 0.75 1.5 2.2 4.0 5.5 7.5 11 15
Rating Type VFS15-
Form 4004PL1-W1 4007PL1-W1 4015PL1-W1 4022PL1-W1 4037PL1-W1 4055PL-W1 4075PL-W1 4110PL-W1 4150PL-W1
Capacity (kVA) Note 1) 1.1 1.8 3.1 4.2 7.2 10.9 13.0 21.1 25.1
Rated output current
(A) Note 2)
1.5
(1.5)
2.3
(2.1)
4.1
(3.7)
5.5
(5.0)
9.5
(8.6)
14.3
(13.0)
17.0
(17.0)
27.7
(25.0)
33
(30)
Rated Output voltage
Note 3)
3-phase 380V to 500V
Overload current rating 150%-60 seconds, 200% -0.5 second
Power
supply
Voltage-frequency 3-phase 380V to 500V - 50/60Hz
Allowable fluctuation Voltage 323V to 550V Note 4), frequency +/-5%
Required Power
supply
capacity (kVA) Note 5)
1.6 2.7 4.7 6.4 10.0 15.2 19.5 26.9 34.9
Protection degree (IEC60529) IP20
Cooling method Forced air-cooled
Color RAL7016
Built-in filter EMC filter

1-phase 240V

Item Specification
Input voltage class 1-phase 240V
Applicable motor (kW) 0.2 0.4 0.75 1.5 2.2
Rating Type VFS15S-
Form 2002PL-W1 2004PL-W1 2007PL-W1 2015PL-W1 2022PL-W1
Capacity (kVA) Note 1) 0.6 1.3 1.8 3.0 4.2
Rated output current
(A) Note 2)
1.5 (1.5) 3.3 (3.3) 4.8 (4.4) 8.0 (7.9) 11.0 (10.0)
Rated Output voltage
Note 3)
3-phase 200V to 240V
Overload current rating 150%-60 seconds, 200%-0.5 second
Power
supply
Voltage-frequency 1-phase 200V to 240V - 50/60Hz
Allowable fluctuation Voltage 170V to 264V Note 4), frequency +/-5%
Required Power
supply
capacity (kVA) Note 5)
0.8 1.4 2.3 4.0 5.4
Protection degree (IEC60529) IP20
Cooling method Self-cooling Forced air-cooled
Color RAL7016
Built-in filter EMC filter

Note 1. Capacity is calculated at 220V for the 240V models, at 440V for the 500V models.
Note 2. Indicates rated output current setting when the PWM carrier frequency (parameter f300) is 4kHz or less. When exceeding 4kHz, the rated output current setting is indicated in the parentheses. It needs to be further reduced for PWM carrier frequencies above 12 kHz.
The rated output current is reduced even further for 500V models with a supply voltage of 480V or more.
The default setting of the PWM carrier frequency is 12kHz.
Note 3. Maximum output voltage is the same as the input voltage.
Note 4. At 180V-264V for the 240V models, at 342V-550V for the 500V models when the inverter is used continuously (load of 100%).
Note 5. Required power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).